Collocation

For those customers who require secured spaces for their network equipment and hardware, we are offering them with rack space with power redundancy and physical security, plus network connections to the internet, either via a shared or dedicated link. With this service, our customers do not have to worry about about finding independent place for their network infrastructure.

Collocation General Specification

  1. 24 x 7 availability.
  2. Physical Security:
    • Guard Patrol System.
    • Intruder Alarm System.
    • CCTV 24 Hours Surveillance System.
  3. N+1 redundancy for critical facility components.
  4. Electrical System 1+1.
  5. Cooling System 1+1.
  6. Concurrent maintenance for electrical and mechanical system.
  7. Compliance to national fire and safety standards (DECAM).

Collocation Features

  1. Power Feeds: One dedicated HT power feed from Singapore Power Grid.
  2. Generators: Two set generator. Diesel fuel tank can be refilled while the generator is running. Diesel fuel refill will be on site 4hrs upon activation.
  3. Uninterrupted Power Supply (UPS):
    • 1+1 system (auto phase synchronized system).
    • (2kW/ rack).
    • 30 Minutes backup at maximum loading.
    • Status of the batteries is monitored by the battery monitoring system.
    • Battery is dry cell type.
    • Finished raised floor height =600mm.
    • Finished raised floor height to ceiling is 2.7 meter.
    • Raised floor loading = 15kN/m2.
    • Data cable ladders, trunking and fiber ducts are mounted under raised floor.
  4. Power Distribution Unit (PDU): PDU shave Residual Current Circuit Breaker (RCCB) installed for each single phase and three phase circuits. PDUs are fed from 1 + 1 UPS systems and are phase synchronized.
  5. Precision Air Cooling: Designed to cater total power dissipation of 2 kW as required. CRAC units and Chilled System are configured as N+1.
  6. Smoke Detection: Intelligent Early Warning Smoke Detector System(Photoelectric).
  7. Fire Suppression: FM-200 gas suppression systems are installed on the ceiling, room and under raised floor.
  8. Premises are also equipped with fire extinguishers, powder and hallotron
    Fire Rating: 1.5 hours fire rated DC perimeter walls and doors in a single FM200 protected area/zone.
  9. Raised Floor:
    • Finished raised floor height =600mm.
    • Finished raised floor height to ceiling is 2.7 meter.
    • Raised floor loading = 15kN/m2.
    • Data cable ladders, trunking and fiber ducts are mounted under raised floor.
  10. Physical Security: The general security system installed at access points will be Proximity Smart Card Access System and CCTV. They will cover critical infrastructure and Entry / Exit doors on24 x 7 x 365 basis.
  11. Other Network Services Available: IP transit, Telin Internet Exchange (TiX),MPLS/VPN-IP Service, Hosting Services (exclude of MRC/TBD).